- All types not listed in this table are not supported in current version.
- The current implementation provides a default mapping rule for each known type, but some new rules might be added in the future and configured using the "
alternate_mapping_rule
" option in its parameters.
Filter interface
The "plugin_ingest
" call will convert each "reading
" of "reading_set
" as follow:
...
- While converting from PIVOT to OPCUA, the PIVOT object is "standalone" and the plugin does not need any configuration from this transformation. The "Exchanged Data" section is only used by conversion from OPCUA to PIVOT.
Filter interface
The <Root> key of PIVOT object can be:
Reading key | Content |
---|---|
PIVOT.GTIS | Tele Signal |
PIVOT.GTIM | Tele Measurement |
PIVOT.GTIC | Tele ControlNot supported |
In the following table: <type>
is equal to
...
The "BscTyp" is not supported currently.
Type of data
The pugin can receive either PIVOT readings that are converted to OPCUA readings or receive OPCUA readings that are converted to PIVOT readings.The plugin is not responsible for checking that the conversion matches its actual role: typically if the plugin is attached to a North OPCUA service, it will be expected to convert OPCUA to PIVOT, but will anyway convert PIVOT to OPCUA if receiving PIVOT instead of OPCUA as reading. This consistency must be ensured by configuration.
Thus the ruls rules for the conversion is:
- For each object in the reading is modified as follow:
- If the object name is "PIVOT" and contains the "GTIM"or "GTIS" key, then the reading must be converted from a PIVOT object to an OPCUA "data object".
- If the object name is "PIVOT" and contains the "GTIC" key, then the reading must be converted from a PIVOT object to an OPCUA "reply object"., convert the PIVOT reading to OPCUA
- If the object name is "controlopcua_objectoperation", convert the OPCUA reading to PIVOT then the reading must be converted from an OPCUA control request (operation) to a PIVOT object.
- Otherwise the reading is not modified.
Converting monitoring data types
For TM/TS, the filter receives PIVOT reading (from south) and creates a corresponding OPC UA reading. The created OPCUA reading has the following JSON equivalent format ("data object"):
Code Block | ||
---|---|---|
| ||
{ "data_object":{ "do_cot": <int>, "do_confirmation": <int>, "do_comingfrom": <string>, "do_id": <string>, "do_type": <string>, "do_quality": <int>, "do_ts_quality": <int>, "do_value_quality": <string>, "do_source": <string>, "do_ts": <int>, "do_ts_org": <string>, "do_ts_validity": <string>, "do_value": <depends on data type...> } } |
...
Converting commands data types
For TC, the filter receives OPCUA reading (from north) and creates a corresponding PIVOT reading.
The content under <Root> will convert the OPCUA command objet to a pivot object as follow:
Converting commands implies two different use case:
- While sending a Fledge "operation" (from North to South). In that case the filter converts an "opcua_operation" into a "PIVOT.GTIC" object.
- While receiving an acknowledgement for a previous "operation" (from South to North). In that case, the filter converts a "PIVOT.GTIC" into a "opcua_reply" object.
The conversion rules are details below.
Conversion from opcua_operation to PIVOT.GTIC
opcua_operation.<...> | PIVOT field ("PIVOT.GTIC" | Key | Type | Default value | opcua.control_object.<...>) | Note | <Root>.Identifier | StringType | Default value | Note |
---|---|---|---|---|---|---|---|---|---|---|
co_id | Identifier | String | PIVOT identifier. | |||||||
co_se | <Root>.Select.stVal | Boolean | false | co_se | - 0 is mapped with false, for Execute - 1 is mapped with true, for Select before Execute | |||||
<Root>N.A. | ComingFrom | String | "opcua" | N.A. | This plugin should always use uses the value "opcua" when converting to pivotPIVOT | |||||
co_type | <Root>.<type> | String | co_type | (see | ||||||
co_test | <Root>.<type>.q.test | Boolean | false | |||||||
co_testts | <Root>.<type>.t.SecondSinceEpoch | Integer | ||||||||
co_ | tsvalue |
| Float | Float 32 | ||||||
co_value | Float 32 |
| String | co_value | intermediate-state | off | on | bad-state | |||||
co_value | <Root>.IncTyp.ctlVal | Integer | Int 32 | |||||||
co_valueInt 32 | <Root>.SpcTyp.ctlVal | Boolean | 0 or 1 | |||||||
co_value | 0 or 1 | <Root>.BscTyp.ctlVal | String | co_value | stop | lower | higher | reserved |
Conversion from PIVOT.GTIC to "opcua_reply"
PIVOT field ("PIVOT.GTIC".<...>) | opcua_reply field | Type | Default value | Note |
---|---|---|---|---|
Identifier | ro_id | String | PIVOT identifier. | |
Cause.stVal | ro_reply | Integer | Converts the values as follow:
| |
<All other fields are ignored> |