The filter implements the Fledge Filter plugin interface (see filter_plugins).

Filter configuration

See Plugins configuration design for examples and details.

The "config" parameter of  "plugin_init" call shall include :

  • A "exchanged_data" category with the same content as provided to the IEC104 south plugin. This section is mandatory so that the filter plugin can convert the PIVOT type from IEC 104 type.

Notes :

  • All types not listed in this table are not supported in current version.
  • The current implementation provides a default mapping rule for each known type, but some new rules might be added in the future and configured using the "alternate_mapping_rule" option in its parameters.

Filter interface

The "plugin_ingest" call will convert each "reading" of "reading_set" as follow:

  • The Reading fields "id", "TimeStamp" and "userTimestamp" are unchanged.
  • The "asset_name" field shall be mapped with "exchanged_data.datapoints.label"
  • The Reading field "reading" is updated with a JSON object {'<Root> key' : {...}} . The content of object under '<Root> key' is given below.

The <Root> key of PIVOT object

...

is:

Reading key

Content

PIVOTTS.GTISTele Signal
PIVOTTM.GTIMTele Measurement
PIVOTTC.GTICNot supported yet

In the following table: <type> is equal to

...

<type> conversion table:

CDC ClassIEC 104 Type IDType ID with timetagAlternative format type id
SpsTypM_SP_NA_1M_SP_TA_1,M_SP_TB_1M_PS_NA_1
DpsTypM_DP_NA_1M_DP_TA_1,M_DP_TB_1M_EP_TA_1,M_EP_TD_1
MvTypM_ME_NA_1M_ME_TA_1,M_ME_TD_1M_ME_ND_1
MvTypM_ME_NB_1M_ME_TB_1,M_ME_TE_1
MvTypM_ME_NC_1M_ME_TC_1,M_ME_TF_1

...


The content under <Root> will convert the IEC 104 data objet to a pivot object as follow:

Key

Type

Default Value

iec104.data_object.<...>

Note

<Root>.Cause.stValIntegerMandatorydo_cotSee Cause of Transmission
<Root>.Confirmation.stValBooleanfalsedo_
confirmation
negative
<Root>.ComingFromStringMandatorydo_comingfrom
Any protocol name ("
iec104
" ,"opcua", ...)
<Root>.IdentifierStringMandatory

do_id

do_type

do_id = PIVOT ID


exchanged_data.datapoints.pivot_id


<Root>.<type>{CDC}Mandatorydo_type
= "opcua_sps" | "opcua_dps" | "opcua_mvi" | "opcua_mvf".Other types not supported in current version.
exchanged_data.datapoints.pivot_type (see <type> conversion table above)

<Root>.<type>.q.DetailsQuality

<Root>.<type>.q.test

<Root>.<type>.q.operatorBlocked


PIVOT : Object
OPCUA : Integer


0do_detail

OR-Mask of following values:

0x0001 = badReference 
0x0002 = failure
0x0004 = inconsistent
0x0008 = innaccurate
0x0010 = oldData
0x0020 = oscillatory
0x0040 = outOfRange
0x0080 = overflow
0x1000 = test
0x2000 = operator blocked


<Root>.<type>.t.TimeQualityInteger0do_ts_quality

OR-Mask of following values:

0x01 = clockFailure
0x02 = clockNotSynch
0x04 = leapSecondKnown


<Root>.<type>.q.SourceString"process" do_source"process" | "substituted"
<Root>.<type>.q.ValidityStringMandatorydo_value_quality"good" | "invalid" | "reserved" | "questionable"
<Root>.<type>.t.SecondSinceEpochInteger0do_ts
<Root>.TmOrgStringMandatorydo_ts_org"genuine" |  "substituted"
<Root>.TmValidityStringMandatorydo_ts_validity"good" | "invalid" | "reserved" | "questionable"
<Root>.SpsTyp.stValBooleanMandatory do_value
<Root>.DpsTyp.stValStringMandatory do_value
See CDC double point status (DPSTyp)


<Root>.MvTyp.mag.fFloatMandatory do_value
<Root>.MvTyp.mag.iIntegerMandatory do_value