Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Module description

TS The dating of status point is always done at the source, by the PA.. If a TS does not have a timestamp, it is automatically timestamped in the PMC. The PMC always leaves the time of the PA for the return of the TS except during the reconstructions for which the TS are returned without date. 

...

The data read from the pivot format isis 

  • For simple type data :
    • PIVOTTS.GTIS.SpsTyp.t.SecondSinceEpoch
  • For double type data :
    • PIVOTTS.GTIS.DpsTyp.t.SecondSinceEpoch

...

  • For simple type data :
    • PIVOTTS.GTIS.SpsTyp.t.SecondSinceEpoch (incremented = timestamp)
    • PIVOTTS.GTIS.SpsTyp.t.TimeQuality = (incremented timestamp)timestamp quality of the PMC
    • PIVOTTS.GTIS.TmOrg.stVal = "substituted" 
    • PIVOTTS.GTIS.TmValidity.stVal = timestamp quality of the PMC
  • For double type data :
    • PIVOTTS.GTIS.DpsTyp.t.SecondSinceEpoch (incremented = timestamp)
    • PIVOTTS.GTIS.DpsTyp.t.TimeQuality = (incremented timestamp)timestamp quality of the PMC
    • PIVOTTS.GTIS.TmOrg.stVal = "substituted"
    • PIVOTTS.GTIS.TmValidity.stVal = timestamp quality of the PMC

If it's impossible to obtain timestamp quality of the PMC from Fledge :

  • the value valid is used for PIVOTTS.GTIS.TmValidity.stVal (or PIVOTTS.GTIS.TmValidity.stVal)
  • PIVOTTS.GTIS.DpsTyp.t.TimeQuality attribute is not used