Attribute | Description | Expected values | Mandatory | ||||
---|---|---|---|---|---|---|---|
name | this identifies the protocol stack | iec104client, iec104server, tase2client, tase2server, 61850client, 61850server, etc... | Yes | ||||
version | version number of the configuration file | 2 digits x.y => x = major change, y = minor change | Yes | ||||
redundancy_groups | array of redundancy groups | Yes | |||||
redundancy_groups.connections | array of connections of a given redundancy group | Yes | |||||
redundancy_groups.connections.clt_ip | address to local IEC 104 client | IP address | Yes | ||||
redundancy_groups.rg_name | this identifies the redundancy group | Yes | |||||
srv_ip | Server IP address | IP address, machine's default IP for a given interface | No | ||||
port | This defines the TCP/IP port to be used by the server. | default = 2404 | No | ||||
tls | activation of TLS (see tls configuration chapter for details) | TRUE, FALSE, default = FALSE | No | ||||
k_value | Maximum number of outstanding (unacknowledged) APDU's at a given time | default = 12 | No | ||||
w_value | Acknowledge the reception latest after this number of APDU's | default = 8 | No | ||||
t0_timeout | time out of connection establishment | default = 30 | No | ||||
t1_timeout | time out for send or test APDU's | default = 15 | No | ||||
t2_timeout | time out for acknowledges in case of no data messages (t2 < t1) | default = 10 | No | ||||
t3_timeout | time out for sending test frames | default = 20 | No | ||||
ca_asdu_size | size of "Common Address of ASDU" | default = 2 (byte) | No | ||||
ioaddr_size | size of 'Information Object Address' | default = 3 (byte) | No | ||||
asdu_size | maximum ASDU size in transmission direction, if set to "0" => maximum possible value is automatically used. | default = 0 (byte) | No | ||||
asdu_queue_size | minimum number of ASDUs that can be stored in the asdu buffer | default = 100 | No | ||||
time_sync | If set on "TRUE" this parameter allows to synchronize the clock of the local computer by the server. If set on "FALSE", the clock is not synchronized. | TRUE, FALSE, default = FALSE | No | ||||
cmd_exec_timeout | Defines the command execution monitoring timeout in milliseconds. The default setting is 20 seconds. | default = 20 seconds (20 000 ms) | No | ||||
cmd_recv_timeout | This parameter defines the highest allowable deviation of received command time tag and local clock. If the difference is too big, command is ignored. | default = 0 (disabled) | No | ||||
accept_cmd_with_time | If set to 0, then accept no commands with timestamp, if set to 1 accept only commands with timestamp, if set to 2, then accept both | default =1 | No | ||||
filter_orig | accept commands only originated from an authorized originator (=TRUE) or accept all originators (=FALSE) | TRUE, FALSE, default = FALSE | No | filter_list | List of Authorized Originators | default = empty | No |
Configuration JSON structure
...