Module description

The gateway south service receives measured values from the AP (south protocol). The station is responsible for the cyclical renewal of the measured valuesstation cyclically according to a predefined period.

The cycling verification period is configurable (30 seconds by default 30 seconds). A measured value is detected as not renewed when if it has not been received during the cycling period.

Following the detection of its non-renewal, it is positioned to "questionable" and the "OldData" detail is positioned in the gateway flag is to true and sent to the controlling centers only once through the north protocolsservice.

When the a new measured value is cycled received again from the station, the measured value is then sent with its new value and its associated quality erase the non-renewal fault. The measured value is then sent with its new values. 

It is the reception of the first message for a measured value that triggers the non-renewal monitoring functionality.

Image Removed

Configuration

A number of parameters must be configured in the module. The configuration is transmitted by PowerConf. 

...

Parameters

...

Description

...

Default value

...

Value range

with the corresponding quality and timestamp.

Measured values cycling OK:

Renewal of measured values okImage Added

Measured values cycling failed:

Image Added

Configuration

AttributeDescriptionExpected valuesMandatory
check_periodcycling check period, in secondsdefault = 30Yes

Configuration JSON structure

Code Block
languagejs
{
   "check_period":{
      "description":"cycling check period in seconds.",
      "type":"integer",
      "default":"30",
      "order":"1",
      "displayName":"Check period"
   }
}

Filtering rules

R1: The measured values cycling check applies only after receiving a first measured value.

R2: The measured values cycling check applies only to measured values with a "cyclical" cause of transmission.

R3: Outside the scope defined by R1 and R2, readings are passed through without any check or change.

Data processing

Input

This filter plugin expects readings to be a pivot model measured values datapoints.

It uses the identification (attribute "PIVOT.GTIM.Identifier") of the datapoint to obtain the context of the measured value in order to :

  • Update the date of reception of the measured value,
  • Know which measured value to read again in order to send the non-renewal message at the end of the timer.

The module uses the data PIVOT.GTIM.Cause.stVal (at "cyclic") to determine if the measured value is configured as cyclic.

Output

In case of non-renewal detection, the last measured value received by the module is re-read and the following values are overwritten :

  • PIVOT.GTIM.MvTyp.q.DetailQuality.oldData is set to "true"
  • PIVOT.GTIM.MvTyp.q.Validity is set to "questionable"
  • PIVOT.GTIM.MvTyp.q.Source is set to "substituted"
  • PIVOT.GTIM.MvTyp.t.SecondSinceEpoch is set to current gateway timestamp
  • PIVOT.GTIM.MvTyp.t.FractionOfSecond is set the fraction of the current gateway second
  • PIVOT.GTIM.TmOrg is set to "substituted"
  • PIVOT.GTIM.TmValidity.stVal is set to "valid"
  • PIVOT.GTIM.Cause.stVal is set to "3" (Spontaneous)


If the timestamp of the gateway is unreliable then:

  • PIVOT.GTIM.MvTyp.t.TimeQuality.clockFailure is set to "true"
  • PIVOT.GTIM.TmValidity is set to "invalid"


If the timestamp of the gateway is is not synchronized with the external UTC time then:

  • PIVOT.GTIM.MvTyp.t.TimeQuality.clockNotSynchronized is set to "true"
  • PIVOT.GTIM.TmValidity is set to "invalid"

...

Cyclic period

...

Period when cycling is expected.

0=cyclic check is disabled

...

30 seconds

[0..3600]

The module does not need the list of measured values, it only monitors the ones it receives. When a measured value is received for the first time the module triggers the monitoring of its non renewal. Only measured values with a TOC of "cyclic" are monitored.

Pivot model interaction

Input

...