Processing is conditioned by the presence of PIVOTTSPIVOT.GTIS.SpsTyp or PIVOTTSPIVOT.GTIS.DpsTyp in incoming data.
...
- For single status point data type :
- PIVOTTSPIVOT.GTIS.SpsTyp.t.SecondSinceEpoch
- For double status point data type :
- PIVOTTSPIVOT.GTIS.DpsTyp.t.SecondSinceEpoch
...
- For single status point data type :
- PIVOTTSPIVOT.GTIS.SpsTyp.t.SecondSinceEpoch is set to current gateway timestamp
- PIVOT.GTIS.SpsTyp.t.FractionOfSecond is set the fraction of the current gateway second
- PIVOTPIVOTTS.GTIS.TmOrg.stVal is set to "substituted"
- PIVOTTSPIVOT.GTIS.TmValidity.stVal is set to "valid"
- For double status point data type :
- PIVOTTSPIVOT.GTIS.DpsTyp.t.SecondSinceEpoch = timestamp is set to current gateway timestamp
- PIVOT.GTIS.DpsTyp.t.FractionOfSecond is set the fraction of the current gateway second
- PIVOTPIVOTTS.GTIS.TmOrg.stVal is set to "substituted"
- PIVOTTSPIVOT.GTIS.TmValidity.stVal is set to "valid"
...
For single status point data type :
- PIVOTTSPIVOT.GTIS.SpsTyp.t.TimeQuality.clockFailure is set to "true"
- PIVOTTSPIVOT.GTIS.TmValidity.stVal is set to "invalid"
For double status point data type :
- PIVOTTSPIVOT.GTIS.DpsTyp.t.TimeQuality.clockFailure is set to "true"
- PIVOTTSPIVOT.GTIS.TmValidity.stVal is set to "invalid"
...
For single status point data type :
- PIVOTTSPIVOT.GTIS.SpsTyp.t.TimeQuality.clockNotSynchronized is set to "true"
- PIVOTTSPIVOT.GTIS.TmValidity.stVal is set to "invalid"
For double status point data type :
- PIVOTTSPIVOT.GTIS.DpsTyp.t.TimeQuality.clockNotSynchronized is set to "true"
- PIVOTTSPIVOT.GTIS.TmValidity.stVal is set to "invalid"
...