Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.
Comment: Corrections mineures

...

  • For single status point data type :
    • PIVOTTS.GTIS.SpsTyp.t.SecondSinceEpoch is set to current gateway timestamp
    • PIVOTTS.GTIS.TmOrg.stVal is set to "substituted"
    • PIVOTTS.GTIS.TmValidity.stVal is set to "valid"
  • For double status point data type :
    • PIVOTTS.GTIS.DpsTyp.t.SecondSinceEpoch = timestamp
    • PIVOTTS.GTIS.TmOrg.stVal is set to "substituted"
    • PIVOTTS.GTIS.TmValidity.stVal is set to "valid"


If the timestamp of the gateway is unreliable then:

For single status point data type :

...

  • PIVOTTS.GTIS.SpsTyp.t.TimeQuality.clockFailure is set to "true"

...

  • PIVOTTS.GTIS.TmValidity.stVal is set to "invalid"

For double status point data type :

...

  • PIVOTTS.GTIS.DpsTyp.t.TimeQuality.clockFailure is set to "true"

...

  • PIVOTTS.GTIS.TmValidity.stVal is set to "invalid"


If the timestamp of the gateway is is not synchronized with the external UTC time then:

For single status point data type :

...

  • PIVOTTS.GTIS.SpsTyp.t.TimeQuality.clockNotSynchronized is set to "true"

...

  • PIVOTTS.GTIS.TmValidity.stVal is set to "invalid"

For double status point data type :

...

  • PIVOTTS.GTIS.DpsTyp.t.TimeQuality.clockNotSynchronized is set to "true"

...

  • PIVOTTS.GTIS.TmValidity.stVal is set to "invalid"